background

Testeur Isolement Fluke 1550C - 5000VAC - 2TO - Précision ±15% - CAT III/IV

  • GLD#
    FLUKE-100053
  • MFG#
    3665021
  • UPC
    095969550918
Min. Order Qty 1
Description
Testeur disolement Fluke, 5000 VCA, résistance de 200 kohms à 2 tohms, résistance de 2 ohms, précision +/- (15 % + 2 v), écran lcd, cote de sécurité  : cat. Iii 1000 v/cat. Iv 600 v, 12 VCC batterie rechargeable au plomb/yuasa np2.Source dalimentation 8-12, ip40 boîtier
Specifications
More Information
UNSPSC41113624
ApplicationFor general circuits, such as switchgear, motors and cables
Accuracy+/- (15% + 2 V)
Display TypeLCD
Resistance2 TOhm
Safety RatingCAT III 1000 V/CAT IV 600 V
Voltage Rating5000 VAC
Power Source12 VDC Lead Acid Rechargeable Battery/Yuasa NP2.8-12
Enclosure TypeIP40
Resistance Range200 kOhm to 2 TOhm
Features
  • Digital insulation testing up to 10 kV
  • Redesigned Fluke® 1550C insulation resistance tester, offers digital insulation testing up to 10 kV, making them ideal for testing a wide range of high voltage equipment including switch gear, motors, generators
  • Long battery life gives the user over 750 tests between charges
  • Automatic calculation of dielectric absorption (DAR) and polarization index (PI) with no additional setup
  • Ramp function for breakdown testing
  • Timer settings up to 99 minutes for timed tests
  • Guard system eliminates the effect of surface leakage current on high resistance measurements
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • 75 x 105 mm LCD, Digital LCD/analog display
  • 2 deg pollution, -20 to 50 deg C temperature rating, IP rating IP40